VARIMETER NA - The grid under control

With its voltage and frequency monitors of the VARIMETA NA series, DOLD offers a safe and standards-conform solution for optimal grid monitoring during energy input into the public grid. The devices are used for voltage and frequency monitoring for decentralised in-house power generation systems. They are very user-friendly and can be configured with only two rotary switches. Thanks to preprogrammed parameters, DOLD voltage and frequency monitors are quickly and easily deployable depending on the respective standard or guideline.
Voltage and frequency monitor RP 9800
• According to DIN EN 60255-1, DIN EN 60947-1
• Voltage and frequency monitoring for generator sets >30 kVA
on public grid, according to VDEW directive
• RP 9800: 3-phase voltage measurement to neutral
• Disconnection on rise and drop of voltage
• Disconnection on rise and drop of frequency
• Disconnection when 10 minute mean value differs to nominal voltage
(overvoltage)
• Frequency and voltage are indicated by separate output relays
• Permits connection or re-connection after adjustable time delay tw
• Protection against manipulation by sealable transparent cover
over setting switches
• Precise adjustment and indication of setting values according to the
directive
• High measuring accuracy
• Width 70 mm
Download datablad
Voltage and frequency monitor acc. to VDE-AR-N 4105 RP 9810
• Certificate of conformity (test certificate) of the BG ETEM
acc. to VDE-AR-N 4105
• Following DIN V VDE V 0126-1-1
• Can be used according to EEG 2012 and SysStabV
• Voltage and frequency monitoring for generator sets >30 kVA on
public grid, as option also for ≤ 30kVA
• Fail-safe because of 2-channel structure
• Certificate of conformity (test certificate) of the BG ETEM
• Monitoring of the section switches with measuring of response time
• System test via test button
• Isolated grid detection
• Manual reset
• With additional enabling input, e.g. for ripple control receiver
• Connection or re-connection after adjustable delay time tw
• Factory setting according to VDE-AR-N 4105
• Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz
for non-regulated power generation systems
• Protection against manipulation by sealable transparent cover
over setting switches
• Additional fault signalling relay output
• High measuring accuracy
• Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)
Download datablad
Voltage and frequency monitor RP 9811
• Certificate of conformity (test certificate) of the BG ETEM
acc. to VDE-AR-N 4105, DIN VDE 0126-1-1, BDEW-directive,
CEI-0-21
• Can be used according to EEG 2012 and SysStabV
• Voltage and frequency monitoring for generator sets
• Fail-safe 2-channel structure
• Monitoring of the section switches by measuring the response time
• System test via test button
• Enabling inputs allow integration into various ripple control and plant
concepts
• Isolated grid detection
• Manual reset
• Memorising of disconnection time
• Connection or re-connection after adjustable delay time tOn
• Factory setting according to:
VDE-AR-N 4105, DIN VDE 0126-1-1, BDEW-directive, CEI 0-21,
ÖVE/ÖNORM, G59/3 LV
• Random controlled disconnection in the range of 50.2 Hz and 51.5 Hz
for non-regulated power generation systems
• Random operated connection time (ton) setting range 60...600 s
• Additional fault signalling relay output
• High measuring accuracy
• Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)